SMART & LOCAL DISPLAY TYPE INFRARED GAS DETECTOR |
Model |
GIR-3000 |
Measuring gas |
Hydrocarbon gases (LNG, LPG, Methane, Buthane & etc) CO2 CO, N2O |
Measuring type |
Diffusion type |
Measuring method |
Infrared type |
Measuring range |
0~100% LEL 0~5000ppm 0~100% Vol 0-2.0% Vol 0-5.0% Vol, 0~4000ppm |
Sensor life time |
Over 5 years |
Response time |
<6sec / 90% scale, <3sec / 50% scale |
Accuracy |
±3% / Full scale |
Parameter control |
Non intrusive control with a Magnet bar (calibration, maintenance, alarm setting) |
Operation mode display |
4-LED (Power, 2-stage alarm, 1-trouble) |
Measuring value display |
LCD display (Built-in back light 2-Line, 16 characters) / OLED Type (Option) |
Alarm signal output |
250V 1A / 3-SPST Relay contact (2-stage alarm, 1-trouble) |
Output signal |
Analog : Measuring signal : 4-20mA DC |
Maintenance signal : 3mA DC |
Calibration signal : 3mA DC |
Fault signal : 0mA DC |
Digital : RS-485 Modbus (Option) |
2mA (HART 7, HART Device Description Language available, Option) |
Cable / Distance |
Power + signal cable : 3 wire >1.5sq(AWG16) / 500m normal |
RS-485 data communication cable : 1 pair (UL2919 RS-485) / 1000m max |
Material |
Housing : ALDC, SUS316(Option) / Sensor : SUS316 |
Conduit connection |
G. Rc. NPT 1/2″, 3/4″ & M20 (G 3/4″ : standard) |
Mounting type |
2″ Pole mount, Wall mount, Duct mount |
Operating temperature |
-20℃ ~ +60℃ / -40℃ ~ +80℃ (Option) |
Operating humidity |
5 ~ 99% RH (non-condensing) |
Operating power |
18 ~ 31V DC (24V DC normal) / 400mA max. |
Dimensions |
156 X 323 X 110 (W X H X D)mm |
Weight |
3kg |
Approval |
Explosion proof type (Ex d IIC T6) KCs / IP66/67 |
Explosion proof type (Ex d IIC Gb T4~T6) ATEX, IECEx |
Explosion proof type (Ex d IIC T6 Gb) NEPSI |
Marine : KR, MED, ABS, DNV |
KFI, CE, HART, SIL 2 |
Reviews